CO Sensor: |
Electrochemical gas sensor |
Range: |
0~100ppm, or other (0-400ppm) |
Accuracy: |
﹤±5% @ 0-400ppm |
Temperature sensor: |
Digital temperature sensor (CMWN)
Thermistor (CMD)
|
Range: |
0~50°C |
Accuracy: |
CMWN:±0.5°C@0~50°C (≥1m/s air flow)
CMD:±0.5°C@25°C (≥1m/s air flow)
|
Output: |
4~20mA (3 wires), 0~10VDC, RS485 / Modbus; OUT1-: T, OUT2: CO |
Relay: |
2×SPST, 1A/30VDC, 0.5A /125VAC(for CMW,CMD),
3A/30VDC, 3A/250VAC (for CMWN)
|
Response Time: |
≤60s |
Output Load: |
≤500Ω (current), ≥2KΩ (voltage) |
Power: |
16~28VAC/16~35VDC (for CMWN)
18~28VAC/18~35VDC (for CMD)
|
Display & Keys: |
optional LCD Display & Keys(CMW/CMWN), see more details on LCD & Keys operation |
Work environment: |
0~50°C (continuous); -5~55°C
(intermittent); 5~99%RH (Non- cond.)
|
Housing: |
ABS+PC (CMWN), ABS(CMD) |
Protection: |
IP30 (CMW/CMWN), IP65 (CMD) |