This robust fixed continuous VOC gas monitor has a selectable detection range of 0 – 10 ppm, 0 – 100 ppm or 0 – 1000 ppm and is ideal for use in manufacturing and process industries where VOCs are typically present. With a 4-20 mA analogue output, the fixed continuous VOC gas detector can be simply integrated into a Distributed Control System (DCS) to provide warnings and enable control of high VOC levels in your working environment.
TVOC 2 Continuous VOC Gas Detector Features:
Ingress Protection Designed to IP65
Sensor ingress protection IP54
Power 5 – 28 VDC Max 130 mA
Output 4-20 mA requires a 8-35 VDC power supply
For IS requirements 8-30 VDC power supply
Range 0 to 10 pp, 0 to 100, 0 to 1000 ppm (user selectable)
Sampling Diffusion (can be pumped if required using an adaptor)
Display 7 segment, 4 digit LCD, 4 colour LEDs
Response Sensor – T90 < 5 secs
Accuracy 0 to 100 ppm: ± 5 % calibration point
100 to 1000 ppm: ± 10 % at calibration points